Optromix Trinius 520

Optromix Trinius 520

Distributed temperature sensing (DTS) system for fire detection

Embedded Trinius 520 measures temperature with 4°F (2.5°С) and 13ft (4m) resolution along an up to 5 miles (8km) long fiber optic cable in a real-time mode. It does not need any technical support during 5 years. This fiber optic cable is not subject to electromagnetic interference, chemical effects and the impact of corrosion. Only one sensing element is used for monitoring. It does not require any extra power supply along the entire length.

Use

Fire alarm DTS system Optromix Trinius 520 could be used in any type of flammable media (gas, gasoline vapours, coal dust etc.) for the realtime temperature control:

  • Fire alarm on long spans (tunnels, factory shops, multistoreyed car parks)
  • Temperature monitoring for underground power lines
  • Temperature control in coal mines
  • Deep-seated fires detection
  • Тemperature monitoring of coal conveyors, oil and gas pipelines condition

Technical specifications

Temperature measurement range -330 to +570°F -200 to +300°С
Spatial accuracy 6.5 ft 2 m
Temperature accuracy 4°F 2.5°С
Line measuring time, sec. from 10
Spatial resolution 6.5 ft 2 m
Sensing element length/cable Up to 5mi Up to 8km
Wavelength, nm/fibre type 1550/MMF, 62.5/125
Usage conditions +15 to +130°F -10 to +55°С
Number of active channels 1
Processing unit dimensions 15.0x10.2x5.1 in 380x260x130 mm
Processing unit weight 8.8lbs 4kg
Power consumption, W 30
Usage conditions, humidity % 0 to 90 (non-condensing)